Search This Blog

_____________________________________________________________

Join Our Site To Subscribe

Wednesday, July 27, 2011

Differences between the emulator and a physical controller

RSLogix Emulate 5000 simulates most of the behaviors of Logix5000 controllers. There are exceptions, and you should keep those exceptions in mind as you use the emulator. The following table shows the differences between Logix5000 controllers and RSLogix Emulate 5000.
WARNING: Do not depend on the emulator to match your physical controller’s performance or operation. Some instructions are interpreted differently in the emulator than in a physical controller, and the execution times for instructions and program files will be significantly different in an emulated controller than in a physical controller.
Features:
Logix5000 Controllers
RSLogix Emulate 5000
Breakpoints and tracepoints
Not supported
Supported (only in ladder diagram programming)
Control real I/O
Supported
Not supported
Forcing
Supported
Supported
Interface to non-Rockwell Software HMI software
DDE/OPC (requires RSLinx Classic Professional, RSLinx Classic Single Node, RSLinx Classic OEM, or RSLinx Classic Gateway; RSLinx Classic Lite does not support DDE or OPC)
DDE/OPC (requires RSLinx Classic Professional, RSLinx Classic Single Node, RSLinx Classic OEM, or RSLinx Classic Gateway; RSLinx Classic Lite does not support DDE or OPC)
Programming languages
Ladder diagram, function block, sequential function chart, and structured text
Ladder diagram, function block, sequential function chart, and structured text
Messaging
Supported
Supported (local only)
Motion instructions
Supported
Supported (virtual axes only)
Jump to subroutines (JSR instructions)
Supported
Supported – however, parameters are passed to the subroutine in reverse order (the last parameter is passed first)
Jump to external routines (JXR instructions)
Supported (in SoftLogix5800 controllers only)
Not supported
Communications through RS232 ports
Supported
Supported
Communications with RSView
Supported
Supported
Time scaling
Not supported
Supported
Single Scan Mode
Not supported
Supported
Network cards
Yes
Not supported
Task priority levels
16
3
Trending
Yes
Yes
Online editing of sequential function chart and structured text programs
Yes
Yes

No comments: