Emulation is simulation of operation -- in the case of RSLogix
Emulate, the software emulates a programmable logic controller.
Search This Blog
_____________________________________________________________
Join Our Site To Subscribe
Labels
- RS Logix Emulate 500 (32)
- RS Logix Emulate 5000 (20)
Monday, September 29, 2014
Monday, September 5, 2011
Program tracepoints
Tracepoints are programmed with
the Tracepoint output instruction (TPT). When the inputs on a rung containing a
TPT instruction are true, the TPT instruction writes a trace entry to a trace
display or log file. (To configure how traces are displayed or logged, see Configure trace displays.)
Programming
the TPT instruction
Programming
the TPT instruction
The Tracepoint (TPT) instruction
has two kinds of parameters:
This parameter:
|
Contains:
|
Requires:
|
Format
|
A string that sets the formatting for the trace reports
(both on-screen and logged to disk).
|
|
Trace This:
|
The tag you want to trace.
|
An INT, BOOL, SINT, DINT, or
REAL tag.
You cannot trace tag
structures (for example, entire timers or counters). However, you can trace
individual structure members.
|
You can trace a large number of
tags with the TPT instruction, but the formatting string can contain only 82
characters. Because two characters are required in the formatting string for
each tag you want to trace, the maximum number of tags you could trace with a
single TPT instruction is 41. However, you will probably want to include spaces
and other formatting to separate tag data in your traces, so the resulting
number of tags that can be traced by one TPT instruction is significantly lower
than 41.
Example:
The following rung triggers a
trace of three analog values when any one of them exceeds a given value
(30.01).
We want to display the tracepoint
information in a particular format. That format is contained in the Format
string (myformat). In this case, the format string contains the following text:
Analog inputs trace:Analog inputs
= %f, %f, and %f
When the tracepoint triggers, the
characters before the colon ("Analog inputs trace") appear in the
title bar of the trace window. The other characters make up the traces. In this
example, the "%f" characters represent the tags to be traced
("analogvalue1," "analogvalue2," and
"analogvalue3"). Click
here for more information about formatting strings.
When this trace is logged to
disk, the characters before the colon appear in the traces. This indicates
which tracepoint caused which trace entry. The following is an example of a
trace entry. "Analog inputs trace:" is the heading text from the
tracepoint's format string.
Analog inputs trace:Analog inputs = 31.00201, 30.282000, and
30.110001
Thursday, August 11, 2011
Configuring a tag in RSView32
Once you have created an OPC node for the emulator, you can add tags from your logic project to your RSView32 tag database. To do this:
- Open your RSView32 project.
- In your project’s System folder, open the Tag Database editor.
- In the Data Source section of the Tag Database editor, click Device.
- Click the button next to the Node Name field. This displays the Node Browser. Select the OPC node you created for the emulator and click OK.
- In the Tag section of the Tag Database editor, select the type of tag you want to create from the Type list.
- In the Data Source section of the Tag Database editor, click the button next to the Address field. This displays the OPC Address Browser.
- In the OPC Address Browser, select the address you want to use with the tag and click OK.
- Finish creating the tag by filling in the fields in the Tag Database editor:
For this field or control:
|
Set or enter:
|
Name
|
The name of the tag you want to create.
|
Security
|
If you have set up security for your RSView32 project, set the security class associated with the tag.
|
Description
|
Type a description of the tag (optional).
|
Minimum
|
The minimum value for the tag (as used in RSView32).
|
Maximum
|
The maximum value for the tag (as used in RSView32).
|
Scale
|
A scaling value for the tag.
|
Offset
|
A value to add to the tag.
|
Units
|
The units for the tag.
|
Data Type
|
Select the data type for the tag.
|
- Click Accept. The tag is stored in the tag database. You can now use the tag in your RSView32 project.